Sensitive and selective detection of plasticizer vapors with modified-SnO2 hollow nanofibers for electrical fire warning
文章来源:SKLFS  作者:SKLFS  发布时间:2020-04-23

Sensitive and selective detection of plasticizer vapors with modified-SnO2 hollow nanofibers for electrical fire warning

Author: Yi, J. X., Chen, W. J., Han, J., Chen, D. D.

Journal: Sensors and Actuators B-Chemical

DOI:  10.1016/j.snb.2019.02.025

KeywordsGas sensor, Fire detection, VOC, Plasticizer, Nanofiber, Chemistry, Electrochemistry

Abstract

Monitoring the vapor concentration of semi-volatile plasticizers released from overheated PVC cables is vital for early warning of electrical fires. In this work, SnO2 hollow nanofibers were prepared and modified with various oxides via a facile impregnation-calcination method. SnO2 hollow nanofibers loaded with 2.8 at.% In2O3 and 5.0 at.% ZnO exhibited excellent response to the fire signature gases, Dioctyl phthalate (DOP) and 2-Ethylhexanol (2-EH) plasticizers, whilst NiO modification deteriorated the sensing performance. A maximum response of 44 and 27 to 100 ppm DOP and 2-EH, respectively, as well as a short response time (3-5 s), were achieved. Moreover, the cross-sensitivity towards common interfering gases such as ethanol and H-2 was greatly reduced. Large-scale simulation tests showed that the modified sensors started to respond to the fire hazard earlier than the alarm of a conventional smoke detector went off, particularly at lower cable temperatures.


 
 
相关链接
Sensitive and selective detection of plasticizer vapors with modified-SnO2 hollow nanofibers for electrical fire warning
联系我们
安徽省合肥市金寨路96号
中国科学技术大学
火灾安全全国重点实验室
邮政编码:230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
火灾科学国家重点实验室 版权所有 皖ICP备:002106505 号