首页  科学研究  学术论文  2016年
 
L. Shi, G. M. Zhang, X. D. Cheng, Y. Guo, J. H. Wang and M. Y. L. Chew (2016) Building And Environment 110 115-128.
文章来源:SKLFS    作者:SKLFS    发布时间:2017-03-14

L. Shi, G. M. Zhang, X. D. Cheng, Y. Guo, J. H. Wang and M. Y. L. Chew (2016) Developing an empirical model for roof solar chimney based on experimental data from various test rigs. Journal/Building And Environment 110 115-128. [In English]
Web link: http://dx.doi.org/10.1016/j.buildenv.2016.10.002
Keywords: Roof solar chimney; Inclination angle; Cavity gap; Solar radiation; Height air gap ratio; Empirical model; NATURAL VENTILATION; AIR-FLOW; TROMBE WALLS; PERFORMANCE; COLLECTOR; SIMULATION; BUILDINGS; CONVECTION; HEIGHT; CAVITY

Abstract: Roof solar chimney is one type of solar chimney to enhance the natural ventilation in buildings. Under the factor that previous studies numerically modelled and validated their results by single test rig, experimental data from all the possible test rigs in the literature were collected and analysed in this study to develop an empirical model for general use. This empirical model was validated by experimental data from various test rigs, with an average error of 14% and up to 144.6% error. Based on the experimental data from different test rigs, the influences of several factors, such as calculated inclination angle (theta', shown in Eq. (6)), cavity gap (d), width (w), height (H), height/cavity gap ratio (Hid), inlet area (A(in)), outlet area (A(out)) and radiation heat (q), on solar chimney performance were addressed. The volumetric flow rate of roof solar chimney showed a linear relationship with w(sin theta')(1/3)q(1/2)d(0.7)H(2/3). The slope of this linear relationship can be determined by test environment, cavity material, glazing, and insulation conditions. Those experimental data within a Hid range of 2.5-103.5 showed that the air velocity increases with a larger Hid, but the volumetric flow rate behaves in an opposite way. It is known from experiments that an equal inlet and outlet area can enhance the flow rate in the cavity and for unequal openings the outlet area showed a relatively higher importance in promoting the air flow. (C) 2016 Elsevier Ltd. All rights reserved.

 
 
相关链接
L. Shi, G. M. Zhang, X. D. Cheng, Y. Guo, J. H. Wang and M. Y. L. Chew (2016) Building And Environment 110 115-128.
联系我们
安徽省合肥市金寨路96号
中国科学技术大学
火灾安全全国重点实验室
邮政编码:230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
火灾科学国家重点实验室 版权所有 皖ICP备:002106505 号