J. Q. Zhang, S. X. Lu, C. H. Li, Q. Li and R. K. K. Yuen (2015) Fire-Induced Temperature Correlations in Ceiling Vented Compartments. Journal/Fire Technology 51 369-379. [In English]
Web link: http://dx.doi.org/10.1007/s10694-014-0386-5
Keywords: Compartment fire; Ceiling vent; Temperature; Correlation; DRIVEN FLOW-THROUGH; COMBINED BUOYANCY; HORIZONTAL VENT; CIRCULAR VENT; PRESSURE; ENCLOSURE; DENSITY; BEHAVIOR; SHALLOW
Abstract: Existing fire-induced temperature correlations are on the basis of vent flow through vertical openings, and are not applicable for ceiling-vented compartment fires. The present work describes a correlation of fire-induced temperature in ceiling-vented compartments based on the widely accepted ceiling-vent flow formula and energy balance. A functional relationship between the dimensionless energy lost through the wall, the energy released through the ceiling vent and the temperature rise was established through theoretical analysis. Experimental tests were conducted on ceiling vented compartments. The averaged temperature rise were obtained, analyzed, and correlated by the established functional relationship. The correlation showed a good agreement with the experimental results. For the ceiling-vented compartment under study (3 x 3 x 1.95 m), the average temperature rise is found to be proportional to 2/3 power of the heat release rate.
 
 
相关链接
J. Q. Zhang, S. X. Lu, C. H. Li, Q. Li and R. K. K. Yuen (2015) Fire Technology 51 369-379.
联系我们
安徽省合肥市金寨路96号
中国科学技术大学
火灾安全全国重点实验室
邮政编码:230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
火灾科学国家重点实验室 版权所有 皖ICP备:002106505 号