首页  科学研究  学术论文  2015年
 
H. Z. Zhao, L. M. Zhao, W. Jiang, J. F. Luo and Y. M. Zhang (2015) Experimental Thermal And Fluid Science 64 108-113.
文章来源:SKLFS    作者:SKLFS    发布时间:2016-02-24
H. Z. Zhao, L. M. Zhao, W. Jiang, J. F. Luo and Y. M. Zhang (2015) Experimental study on vertical RPU fire suppression performance using water spray. Journal/Experimental Thermal And Fluid Science 64 108-113. [In English]
Web link: http://dx.doi.org/10.1016/j.expthermflusci.2015.02.012
Keywords: RPU; Vertical fire; Water spray; Suppression; MIST; EXTINGUISHMENT
Abstract: A series of vertical fire suppression experiments are conducted using rigid polyurethane (RPU) material of dimensions 60 x 30 x 2 cm in the standard combustion chamber. Four different kinds of water spray fluxes (66.7, 80, 90, 100 ml/min) and two different spray angles (0 degrees and 30 degrees) are used to suppress wind-aided RPU fire. The thermal radiation, carbon monoxide concentration and smoke concentration are measured with water spray being applied or not. The results show that both of the maximum radiation and maximum smoke concentration appear to have minimum values with 90 ml/min water spray flux and 0 degrees water spray angle. In addition, all the obtained values of the maximum radiation, maximum carbon monoxide concentration, extinguishing time and maximum smoke concentration with 0 degrees spray angle are larger than those with 30 degrees spray angle with the same water spray flux. That is, for the same water spray flux, the suppression effect with 30 degrees spray angle is better than that with 0 degrees spray angle. (C) 2015 Published by Elsevier Inc.
 
 
相关链接
H. Z. Zhao, L. M. Zhao, W. Jiang, J. F. Luo and Y. M. Zhang (2015) Experimental Thermal And Fluid Science 64 108-113.
联系我们
安徽省合肥市金寨路96号
中国科学技术大学
火灾安全全国重点实验室
邮政编码:230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
火灾科学国家重点实验室 版权所有 皖ICP备:002106505 号