首页  科学研究  学术论文  2015年
 
P. Zhu, X. S. Wang, Z. G. Wang, H. Y. Cong and X. M. Ni (2015) Journal Of Fire Sciences 33 269-289.
文章来源:SKLFS    作者:SKLFS    发布时间:2016-02-23
P. Zhu, X. S. Wang, Z. G. Wang, H. Y. Cong and X. M. Ni (2015) Experimental and numerical study on attenuation of thermal radiation from large-scale pool fires by water mist curtain. Journal/Journal Of Fire Sciences 33 269-289. [In English]
Web link: http://dx.doi.org/10.1177/0734904115585796
Keywords: Water mist curtain; thermal radiation attenuation; large pool fire; computational fluid dynamics; SPRAY CURTAIN; HEAT-TRANSFER; SUPPRESSION
Abstract: Full-scale experiments and numerical simulations were conducted to study the thermal radiation attenuation from large fires by water mist curtain with low and intermediate pressures. Fire dynamics simulator (version 6) was used for numerical simulations. A novel multi-injector nozzle was designed to generate a homogeneous water mist curtain with low water consumption. Water mist characteristics of one of the injectors were measured by Shadowgraphy technology. A 1x1m diesel pool fire was considered as the fire source. The experimental results show that the water mist curtain has high thermal radiation attenuation efficiency, for example, about 82.7% radiant heat flux could be attenuated by the water mist curtain with 2MPa working pressure and flow rate of 13.3L/min. Comparisons with the experimental results show that the calculated radiant heat flux and temperature are slightly underestimated.
 
 
相关链接
P. Zhu, X. S. Wang, Z. G. Wang, H. Y. Cong and X. M. Ni (2015) Journal Of Fire Sciences 33 269-289.
联系我们
安徽省合肥市金寨路96号
中国科学技术大学
火灾安全全国重点实验室
邮政编码:230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
火灾科学国家重点实验室 版权所有 皖ICP备:002106505 号