首页  科学研究  学术论文  2002年
 
Li YZ, Huo R, Chow WK (2002) Journal of Fire Sciences 20(1), 37-51.
文章来源:WOS    作者:SKLFS    发布时间:2011-08-16

Li YZ, Huo R, Chow WK (2002) On the operation time of horizontal ceiling vent in an atrium. Journal of Fire Sciences 20(1), 37-51. [In English]

Web link: http://dx.doi.org/10.1177/0734904102020001831

Keywords:

ventilation; enclosure; behavior;

Abstract: Smoke control by a horizontal ceiling vent in an atrium is studied in this paper. A bi-directional airflow moving upward and downward across the vent might be observed and this would affect the efficiency of smoke extraction. Whether the flow is bi-directional or uni-directional depends on the pressure difference across the vent upon activation. Before opening the horizontal ceiling vent, the pressure difference should be higher than a critical value. Thickness of the smoke layer formed under the ceiling before opening the vent is found to be important. The required smoke layer thickness for getting such a critical pressure is discussed in this paper. Two situations of no temperature difference between the inside and outside of the atrium; and the outside temperature is higher than the inside temperature, are considered.

 
 