Zhang YF, Fang YD, Xin HA, Jin XA, Jun Q (2007) Process Safety and Environmental Protection 85(B1), 39-44.
文章来源:WOS    作者:SKLFS    发布时间:2011-08-16

Zhang YF, Fang YD, Xin HA, Jin XA, Jun Q (2007) Experimental study of the interaction between the water mists and PVC fire. Process Safety and Environmental Protection 85(B1), 39-44. [In English]

Web link: http://dx.doi.org/10.1205/psep05015

Keywords:

PVC fire; water mists; interaction; heat release rate; toxic gases; sprays

Abstract: Effect of water mist on the small-scale solid fuel polyvinyl chloride (PVC) fire in the confined space has been studied experimentally with the heat release rate measured by a cone calorimeter in this paper. The water mist is generated by a single pressure nozzle and the diffusion flame is produced from PVC samples respectively. The LDV/APV system is employed to determine the water mist characteristics. The Cone Calorimeter is used to measure the heat release rate, oxygen and carbon monoxide concentrations and other important parameters of the interaction under various conditions. The results of the test showed that heat extraction cooling (flame cooling and fuel surface cooling) plays a dominating role to suppress the PVC fire, when the water mist with enough volume flux are applied to the diffusion flame in the confined space. The higher the operation pressure, the easier the suppression. The faster the PVC fire suppressed by water mist with large enough water flux, the less the total amount of toxic gases (CO, CO2) produced.

 
 
相关链接
Zhang YF, Fang YD, Xin HA, Jin XA, Jun Q (2007) Process Safety and Environmental Protection 85(B1), 39-44.
联系我们
安徽省合肥市金寨路96号
中国科学技术大学
火灾安全全国重点实验室
邮政编码:230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
火灾科学国家重点实验室 版权所有 皖ICP备:002106505 号