Li KY, Huo R, Ji J, Ren BB (2010) Journal of Hazardous Materials 174(1-3), 512-521.
文章来源:WOS    作者:SKLFS    发布时间:2011-08-15
Li KY, Huo R, Ji J, Ren BB (2010) Experimental investigation on drag effect of sprinkler spray to adjacent horizontal natural smoke venting. Journal of Hazardous Materials 174(1-3), 512-521. [In English]

Web link: http://dx.doi.org/10.1016/j.jhazmat.2009.09.082

Keywords:

Sprinkler spray; Smoke venting; Drag force; Buoyancy; Smoke venting; logging; Fire; compartment fire environment; model; layer; 1st

Abstract: Discharge rate of a horizontal adjacent smoke vent under sprinkler spray is experimentally investigated. Temperature of smoke layer and velocity of smoke venting were measured, under different sprinkler operating pressures and smoke venting areas. CO concentration at the smoke vent center and velocity of vent flow with fresh air outside were recorded in tests under different smoke venting conditions. Experimental results have shown that efficiency of smoke venting is controlled by a combination of smoke buoyancy and drag force of sprinkler spray. Only when buoyancy is greater than drag force the smoke could be extracted by venting. Velocity of smoke venting has shown to decrease as the operating pressure increases. Smoke venting logging, which represents the failure of smoke venting,was experimentally found from certain operating pressure called initial logging pressure. The CO concentration was found to increase after sprinkler was operated as the smoke is constrained in the spray region with horizontal momentum decreased. Negative pressure difference is caused at the vent when there is smoke venting logging, which might practically bring the exterior fresh air into the fire building. Additionally, experiments results have shown that the venting area has little influence on smoke flow under smoke venting logging. (C) 2009 Elsevier B.V. All rights reserved.

 
 
相关链接
Li KY, Huo R, Ji J, Ren BB (2010) Journal of Hazardous Materials 174(1-3), 512-521.
联系我们
安徽省合肥市金寨路96号
中国科学技术大学
火灾安全全国重点实验室
邮政编码:230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
火灾科学国家重点实验室 版权所有 皖ICP备:002106505 号