首页  科学研究  学术论文  2010年
 
Xu QA, Griffin GJ, Jiang Y, Jin C (2010) Thermal Science 14(2), 521-531.
文章来源:WOS    作者:SKLFS    发布时间:2011-08-14
Xu QA, Griffin GJ, Jiang Y, Jin C (2010) AN EVALUATION OF THE BFD CURVE BASED UPON WOOD CRIB FIRES PERFORMED IN AN ISO9705 ROOM. Thermal Science 14(2), 521-531. [In English]

Web link: http://dx.doi.org/10.2298/tsci1002521x

Keywords:

compartment temperature; wood crib fire; ISO 9705 room; BFD curve

Abstract: The BFD curve fitting method of Barnett is adopted to study the compartment temperature-time curves for a series of wood crib fires in an ISO 9705 room. The nominal fire sizes were 0.15 MW, 0.25 MW, 0.5 MW. and 1.0 MW. The cribs were positioned at the corner or the center of the floor of the room. The temperatures within the compartment were measured using two thermocouple trees with 10 thermocouples on each tree; these measured the compartment temperature from floor to ceiling. No flashover occurred during the tests, and the compartment temperature can be well described by a two-zone model. BFD curve fitting was performed for all 20 temperature-time curves in the upper and lower zones of the compartment for each test. The fitting error is evaluated for all tests. This empirical model needs more tests to verify and optimize.

 
 
相关链接
Xu QA, Griffin GJ, Jiang Y, Jin C (2010) Thermal Science 14(2), 521-531.
联系我们
安徽省合肥市金寨路96号
中国科学技术大学
火灾安全全国重点实验室
邮政编码:230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
火灾科学国家重点实验室 版权所有 皖ICP备:002106505 号