首页  科学研究  学术论文  2011年
 
Huang X, Wang XS, Liao GX (2011) Proceedings of the Combustion Institute 33, 2573-2579.
文章来源:   作者:   发布时间:2011-08-13

Huang X, Wang XS, Liao GX (2011) Characterization of an effervescent atomization water mist nozzle and its fire suppression tests. Proceedings of the Combustion Institute 33, 2573-2579. [In English]

Web link: http://dx.doi.org/10.1016/j.proci.2010.06.001

Keywords:

Effervescent atomization; Two-phase flow; Water mist; Fire suppression; pool fires; flow

Abstract: A gas-outside-liquid-inside water mist nozzle based on effervescent atomization technology is designed, characterized and tested in this paper. The droplets size distribution, velocity under different operation pressures and gas-liquid-ratios (GLR) are measured with a Phase Doppler Analyser (PDA). The gas flow rate, liquid flow rate of the nozzle with one or seven orifices are also characterized under different operation pressures and GLR conditions, respectively. The results show that all of above parameters are mainly influenced by GLR, i.e., the larger the GLR is, the smaller the droplet size will be, and the liquid mass flow rate is exponentially increased with the increasing of GLR. The test results of fire suppression show that this gas-outside-liquid-inside effervescent atomizer works well for fire extinguishment except the cases where the liquid flow rate is less than about 70 kg/h and the gas pressure is lower than 0.3 MPa. (C) 2010 The Combustion Institute. Published by Elsevier Inc. All rights reserved.

 
 
相关链接
Huang X, Wang XS, Liao GX (2011) Proceedings of the Combustion Institute 33, 2573-2579.
联系我们
安徽省合肥市金寨路96号
中国科学技术大学
火灾安全全国重点实验室
邮政编码:230026
   
Tel:(+86)551 63601651
Fax:(+86)551 63601669
E-mail:sklfs@ustc.edu.cn
Copyright © 1990-2011 State Key Laboratory of Fire Science, University of Science and Technology of China
火灾科学国家重点实验室 版权所有 皖ICP备:002106505 号